Modular fire water tanks are reservoirs that supply water to fire suppression systems, built by joining galvanized, GRP composite, specially coated or stainless steel panels on a plastic base. Because panel dimensions are produced in multiples of 1075 mm, a tank can be enlarged to the volume required by adding modules, and it is easier to transport to site and install than a single-piece reinforced concrete or sheet-steel tank. Together with the pump room, this structure forms the water source for sprinkler, fire hydrant and fire hose cabinet lines, and it is designed in integration with the fire pump set and fire water tank sections on the Mechanical Systems page.
Modular tanks do not have to be squeezed into a single rectangular volume; they can be designed in L, H, U or triangular forms to fit project-specific and irregular spaces such as under stairs, under garage ramps, between columns and under beams. The capacity range extends from 1,250 liters (1075×1075×1075 mm) to 200,000 liters (9675×9675×2150 mm), and intermediate capacities are achieved by adding or removing modules; for sites with limited space, 5,000, 7,500 and 12,500 liter "Eco" variants are offered with a lower profile. The same product family can therefore meet the water reserve needs of both large facilities and existing buildings with tight space.
The volume required for the fire reserve is determined by hydraulic calculation based on the flow and duration requirements of TS EN 12845 and BYKHY (Turkish Fire Protection Regulation); the modular tank provides this calculated volume in a form and capacity that fits the site's existing layout. In conventional black sheet-steel tanks the paint usually flakes off quickly and rusting begins, concrete tanks without ceramic lining can harbor bacteria, and plastic tanks can grow algae in sunlight. The modular panel construction, with no sharp corners, prevents sediment and bacteria buildup; this hygiene advantage is also valuable in potable and utility water tanks beyond fire reserves, and the tank is operated within the same maintenance and inspection cycle as the fire pump.